Артикул | GK24G-MF |
Вспомогательные переключатели | Нет |
Кабель | 1 м, 4 x 0.75 мм |
Крутящий момент | 40 Нм |
Питание | 24 В~/= |
Площадь заслонки | 8 м |
Присоединение | Универсальный захват |
Серия | GK_G |
Управление | Плавное 0…10 В= Рабочий диапазон 2…10 В= Настраивается |
Electrical data | |
Nominal voltage | AC 24 V, 50/60 Hz / DC 24 V |
Nominal voltage range | AC 19.2 ... 28.8 V / DC 21.6 ... 28.8 V |
Power consumption In operation At rest For wire sizing |
11 W @ nominal torque 3 W 21 VA (lmax 20 A @ 5 ms) |
Connection | Cable 1 m, 4 x 0.75 mm2 (halogen-free) |
Parallel operation | Yes (note the performance data) |
Functional data | |
Torque Inhibiting torque |
40 Nm 40 Nm |
Control Control signal Y Operating range |
DC 0 … 10 V, input impedance 100 k DC 0.5 ... 10 V |
Position feedback (Measuring voltage U) | DC 0.5 ... 10 V, max. 0.5 mA |
Setting emergency position (POP) | 0% (POP rotary button end stop, left) |
Bridging time (PF) | 2 s |
Position accuracy | ±5% |
Direction of rotation Motor Emergency setting position |
As an option with / Reversible with switch 0 ... 100% |
Direction of rotation Y = 0 V | At switch position 1 or 0, respectively |
Manual override | Gearing latch disengaged with push button |
Angle of rotation | Max. 95°, can be limited at both ends with adjustable mechanical end stops |
Running time Standard operation Emergency setting position |
150 s / 90° 35 s @ 0 ... 50°C |
Automatic adjustment of running time, operating range and measuring signal U to match the mechanical angle of rotation | Manual triggering of the adaption by pressing the «Adaption» button |
Override control |
MAX (maximum position)= 100% MIN (minimum position)= 0% ZS (intermediate position, only AC)= 50% |
Sound power level Standard operation Emergency setting position |
53 dB (A) @ 90 s running time 52 dB (A) @ 150 s running time 61 dB (A) |
Service life Design life Full cycles Part cycles |
15 years 100,000 1,000,000 |
Position indication | Mechanical, pluggable |
Terms and abbreviations | |
POP = Power off position / emergency setting position | PF = Power fail delay time / bridging time |
Safety | |
Protection class | III Safety extra-low voltage UL Class 2 Supply |
Degree of protection | IP66 NEMA 4, UL Enclosure Type 4 |
EMC | CE according to 2004/108/EC |
Certification | Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14 cULus according to UL 60730-1A and UL 60730-2-14 and CAN/CSA E60730-1:02 |
Mode of operation | Type 1.AA |
Rated impulse voltage | 0.8 kV |
Control pollution degree | 4 |
Ambient temperature | –30 ... +50°C |
Non-operating temperature | –40 ... +80°C |
Ambient humidity | 100% r.h. |
Maintenance | Maintenance-free |
Dimensions / Weight | |
WDimensions | See «Dimensions» on page 8 |
Weight | Approx. 4.8 kg |