Артикул | LHQ24A-SR100 |
Вспомогательные переключатели | Нет |
Кабель | 1 м, 4 x 0.75 мм |
Крутящий момент | 100 Н |
Питание | 24 В~/= |
Площадь заслонки | 0,7 м |
Присоединение | Шток |
Серия | LHQ |
Управление | Плавное 0…10 В= Рабочий диапазон 2…10 В= |
Electrical data | |
Nominal voltage | AC 24 V, 50/60 Hz / DC 24 V |
Nominal voltage range | AC 19.2 ... 28.8 V / DC 21.6 ... 28.8 V |
Power consumption In operation At rest For wire sizing |
13 W @ nominal torque 2 W 23 VA (I max. 20 A @ 5 ms) |
Connection | Cable 1 m, 4 x 0.75 mm2 |
Functional data | |
Actuating force | Min. 100 N @ nominal voltage |
Control Control signal Y Operating range |
DC 0 ... 10 V, input impedance 100 k DC 2 ... 10 V |
Position feedback (Measuring voltage) | DC 2 ... 10 V, max. 0.5 mA |
Position accuracy | ±5% |
Direction of stroke | Reversible with switch 0 / 1 |
Direction of stroke at Y = 0 V | At switch position 1 resp. 0 |
Manual override | Gearing latch disengaged with pushbutton, can be locked |
Stroke adjustment | 20 ... 100 mm, adjustable in 20 mm-steps, can be limited at both ends with mechanical end stops |
Stroke limiting | Min. 40 mm |
Running time | 3.5 s / 100 mm |
Automatic adjustment of operating range and measuring signal U to match the mechanical stroke adjustment | Manual triggering of the adaption by pressing the «Adaption» button |
Override control |
MAX (maximum position)= 100% MIN (minimum position)= 0% ZS (intermediate position, only AC)= 50% |
Sound power level | 52 dB (A) |
Negative torque ! | 50% from nominal torque (Caution: can only be used with restrictions. Please contact your Belimo representative.) |
Safety | |
Protection class | III Safety extra-low voltage UL Class 2 Supply |
Degree of protection | IP54 in any mounting position NEMA 2, UL Enclosure Type 2 |
EMC | CE according to 2004/108/EC |
Certification | Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14 cULus according to UL 60730-1A and UL 60730-2-14 and CAN/CSA E60730-1:02 |
Mode of operation | Type 1 |
Rated impulse voltage | 0.8 kV |
Control pollution degree | 3 |
Ambient temperature | –30 ... +40°C (no restrictions) +40 ... +50°C (Caution: can only be used with restrictions. Please contact your Belimo representative.) |
Non-operating temperature | –40 ... +80°C |
Ambient humidity | 95% r.H., non-condensating |
Maintenance | Maintenance-free |
Dimensions / Weight | |
Dimensions | See «Dimensions» on page 6 |
Weight | Approx. 640 g |